Gambar halaman
PDF
ePub

were operated with success from the Edison threewire system. These can, therefore, hardly be held responsible for the difference in the commercial results obtained with the two systems.

As I have said, the ends in view in the development of the two systems have been radically different. The one was to produce a given amount of light for the minimum of investment; the other was to provide a permanent investment that would render the maximum of profit. These standpoints in general mark the difference between the manufacturer and the user, and we find these two systems developed in this way,-one almost entirely by the manufacturer, and the other by the combined efforts of the various users. The results are the natural effects of progression along these lines.

Few opportunities have we had of comparing the two systems from the same standpoint and under like conditions. The purpose of this paper is to show the alternating current applied from the same standpoint, compelled to fulfill the same conditions, and then to compare the results with the best produced with

direct current.

To better contrast the different methods of distribution, we will review briefly those in general use before describing the most recent developments.

The early alternating-current stations were installed on the principle that the drop in lines with distribution at 1,000 volts was so small that it was practically negligible. Two wires were accordingly run out from the station, passing along those streets where light was to be furnished, and lights were connected ad libitum at any desired points between the station. and the farthest end, without reference to such trifling considerations as difference in potential. Distribution

was attempted in this way for years, and in many places is still in operation. Lines are even being constructed to-day without any notion of a system of feeders and mains, although an almost perfect system for the maintenance of uniform pressure

was in operation in many Edison stations before the first alternating station was in existence. Fortunately for the operators of such models of simplicity, the current delivered has usually been so small in quantity that with the proverbial No. 6 wire, which seemed to possess virtues not affected by distances, the difference of pressure between neighboring customers rarely exceeded ten per cent.

A few more enlightened experts-plants were always installed by experts in the early days-eventually conceived the novel idea that if the drop, a little of which they had discovered by that time, could be confined to a greater extent to those portions of the lines where there were no lights, some might be spared from the lighting districts. A few feeder lines were therefore stuck in here and there to boost up the pressure where it was lowest.

The regulation was all effected by means of the dynamo field rheostat, and the pressure indicated by a voltmeter on the secondary of a transformer whose primary was connected to the 'bus bars on the switchboard. A few lamps were also often operated by the same transformer to light the switchboard or other parts of the station. The station attendant was, of course, in absolute ignorance of the pressure at any point on the lines where lamps were used. The pressure was therefore usually run high enough to be on the safe side. The attendant was was sometimes instructed to let his voltmeter needle follow gently the manoeuvres of his ammeter, as there was thought

to be a more or less intimate connection between volts and amperes and the volts ought not allowed to get too far behind.

to be

If any one ever breathed a suggestion of pressure wires, it was probably his last breath. At any rate, he was never heard of again. What! pressure wires with alternating current? Preposterous idea. Alternating and progression were considered almost synonymous terms. Antiquated ideas must be abandoned.

This faintly-whispered need might, however, be heard again, so, to meet the emergency, a compensating voltmeter was produced that could be adjusted for any drop in the lines. It was ingeniously arranged so that a small series transformer in the main line would send currents opposing those operating the voltmeter, thereby making the needle or index drop back approximately proportionately to the current in the line. This device was a great help, and caused the drop in lines to jump into prominence at once. It would be quite perfect if the drop in alternatingcurrent lines were proportional to the current, but it is not. The power factor of ordinary alternatingcurrent systems is usually quite low at light loads, and, except with very small wire, an ampere may therefore produce much more drop proportionately at light load than at heavy load.

One alternating-current station of which I have intimate knowledge, has used pressure wires in connection with each feeder for years. There may be a few others, but they are rare exceptions even to-day. The usual system of distribution provides a separate transformer for each customer. In many cases, this implies the use of a very small transformer. It is impossible to make the efficiency of small transformers high. As each customer may at times use

1

all of his lamps, he must have full transformer capacity for such an emergency. The ordinary ratio between maximum station loads and the number of lamps connected, is in most cases under fifty per cent where meters are employed. The transformers then being of a total capacity equal to the number of lamps connected, average at best only fifty per cent of their rated capacity at the maximum station load. In most stations the average load generated is much less than twenty-five per cent of the maximum load, and, therefore, with twice the transformer capacity of that represented by maximum station load, the average transformer load would not exceed ten per cent of the transformer capacity, all the year round.

The efficiency of the average modern transformer of usual size at ten per cent of its rated load is not over sixty-five per cent, and the average of transformers at present in use not more than fifty per cent. It is perfectly safe to say that there is not an alternating-current station to-day using individual transformers for each or neighboring customers that can show an average efficiency of distribution of over sixty per cent, and few that can show over fifty per

cent.

In Europe, it is, to some extent, the practice to use transformer sub-stations with low-potential distribution from these points. Transformers are cut in and out at these sub-stations by attendants according to the demand for current. It is doubtful if, after paying interest on the investment in property and housing for these transformer stations, together with the investment in instruments and switches required, and the attendants' wages, there is very much saving effected. Had we nothing better to turn to than these systems, the cost of distribution from large stations

would be extreme compared with the direct-current, Edison three-wire system, and competition with the latter could not be a success.

Another very important consideration is the economy or efficiency of lamps used. To employ successfully the highest-economy lamp made, a very uniform pressure must be maintained. With the usual alternating-current system, and with an equally good disposition of feeders and mains, the variations of pressure will exceed those in a direct-current system by nearly three per cent, on account of the transformer drop, and to secure even this limit of variation, pressure wires must be used with each feeder.

It is not surprising to find, therefore, that almost all alternating-current stations are using lamps requiring twenty per cent more current than those used by direct-current stations.

I cannot refrain from remarking here that to operate any station, alternating or direct-current, without pressure wires, is to be worse than penny-wise and pound-foolish. In any alternating-current station employing overhead wires, the saving in lamp renewals would equal the cost of pressure wires in little over a month's time. I might also add that the total loss of lamps is not the most serious result of variations in pressure. Such variations cause a rapid decline in candle power, and low candle power means. disaffection of customers and the increased use of gas.

Now, let us leave for the time the alternatingcurrent station and its usual system of distribution, and adjourn to a modern Edison station, to see if there can really be anything learned from so antiquated a source. On entering, we see at first large direct-connected generators running in multiple. We have also also seen those in a few alternating-current

« SebelumnyaLanjutkan »